Enter the airflow and either a design friction rate or a maximum air velocity. This ductulator returns the round duct diameter, the next common size, rectangular ducts with the same pressure loss, and the velocity and friction you will actually get at each size. It works in CFM and inches or in m³/h and millimetres.
Air at 20 °C (68 °F) at sea level. Straight duct only: add fittings separately.
| Width × height | Aspect ratio | Equivalent round | Velocity | Friction rate |
|---|
Widths are rounded up to the next 2 in (50 mm), so each rectangle has a slightly lower friction rate than the target. Aspect ratios above 4:1 are left out.
With a design friction rate of 0.073 in. w.g. per 100 ft, the calculator gives an exact diameter of 10.35 in. Energy Vanguard ran the same 400 CFM at 0.073 through the ASHRAE duct calculator wheel and needed “a round metal duct that’s slightly larger than 10″”. In a 10 in duct the air moves at 733 fpm with 0.086 in. w.g. per 100 ft, which is fine for a supply run. A return carrying 400 CFM needs a 12 in duct (509 fpm, 0.036 in. w.g. per 100 ft) to stay under the 700 fpm return limit.
At 0.8 Pa/m in galvanized steel, 1,000 m³/h needs 286 mm. The next common size is 315 mm: 3.56 m/s and 0.50 Pa/m. A 400 × 200 mm rectangle has the same friction as a 305 mm round duct.
The friction rate is not a constant you pick from a chart. ACCA’s Manual D calculates it from two numbers: the available static pressure (ASP) and the total effective length (TEL) of the longest run.
“The available static pressure (ASP) is what’s left when you take the total external static pressure and subtract the pressure drops for all the things that aren’t ducts and fittings.” – ACCA, Calculating Friction Rate – It’s Not a Constant (2017)
“The total effective length (TEL) is the sum of the duct lengths and the fitting equivalent lengths.” – ACCA (2017)
Friction rate (in. w.g. per 100 ft) = ASP × 100 ÷ TEL
Many installers skip the calculation and use 0.1 in. w.g. per 100 ft. ACCA explains that 0.1 sits in the middle of the Manual D chart, which is why it became a habit, and that in one worked design “if you use 0.1 instead of 0.073, your ducts will be undersized.” Use the calculated value when you have it, and 0.1 only for a first estimate.
| in. w.g. per 100 ft | Pa per metre |
|---|---|
| 0.05 | 0.41 |
| 0.08 | 0.65 |
| 0.10 | 0.82 |
Sizing by friction alone can leave air moving too fast. Energy Vanguard summarises the residential limits in ACCA Manual D: “In Manual D, Table N3-1 specifies the maximum velocities for supply and return trunks and branches. For supplies, it’s 900 fpm. For returns, it’s 700 fpm.” That is 4.6 m/s and 3.6 m/s. The calculator warns you when the size you picked is above either limit. Commercial and industrial ducts are often designed faster, so use the limit your project specifies.
Galvanized round duct, sized at 0.1 in. w.g. per 100 ft and rounded up to the next common size (1 in steps up to 10 in, then 2 in steps).
| ปริมาณลม | Exact diameter | Duct size | Velocity at that size |
|---|---|---|---|
| 100 CFM | 5.8 in | 6 in | 509 fpm |
| 200 CFM | 7.5 in | 8 in | 573 fpm |
| 400 CFM | 9.7 in | 10 in | 733 fpm |
| 600 CFM | 11.3 in | 12 in | 764 fpm |
| 800 CFM | 12.6 in | 14 in | 748 fpm |
| 1,000 CFM | 13.6 in | 14 in | 935 fpm |
| 1,500 CFM | 15.9 in | 16 in | 1,074 fpm |
| 2,000 CFM | 17.7 in | 18 in | 1,132 fpm |
The same in metric, sized at 0.8 Pa/m:
| ปริมาณลม | Exact diameter | Duct size | Velocity | Friction at that size |
|---|---|---|---|---|
| 100 m³/h | 122 mm | 125 mm | 2.26 m/s | 0.70 Pa/m |
| 200 m³/h | 157 mm | 160 mm | 2.76 m/s | 0.73 Pa/m |
| 300 m³/h | 183 mm | 200 mm | 2.65 m/s | 0.52 Pa/m |
| 500 m³/h | 221 mm | 250 mm | 2.83 m/s | 0.44 Pa/m |
| 1,000 m³/h | 286 mm | 315 mm | 3.56 m/s | 0.50 Pa/m |
| 1,500 m³/h | 332 mm | 355 mm | 4.21 m/s | 0.58 Pa/m |
| 2,000 m³/h | 370 mm | 400 mm | 4.42 m/s | 0.55 Pa/m |
| 3,000 m³/h | 431 mm | 450 mm | 5.24 m/s | 0.65 Pa/m |
A rectangular duct carrying the same airflow with the same friction is not the one with the same area. Huebscher’s equation gives the round diameter with equal friction:
De = 1.30 × (a × b)^0.625 ÷ (a + b)^0.25
A 10 × 16 in duct, for example, behaves like a 13.7 in round duct. For a 300 mm round duct (0.071 m² of area, 0.94 m of perimeter), the equal-friction rectangles in 50 mm steps are 400 × 200 mm (0.080 m², 1.20 m) and 300 × 300 mm (0.090 m², 1.20 m). The rectangle always needs more sheet metal per metre. The flatter it gets, the more it needs, so keep the aspect ratio low when the ceiling allows.
Rougher walls need bigger ducts. The calculator uses the roughness classes from Caleffi’s duct pressure loss handbook: 0.03 mm for PVC and aluminium, 0.09 mm for galvanized and stainless steel, 0.9 mm for lined ducts and 3.0 mm for flexible ducts. For 720 m³/h at 0.8 Pa/m, that means 250 mm in PVC, 253 mm in galvanized steel, 268 mm in lined duct and 282 mm in flexible duct.
Flexible duct is only as good as its installation. HPAC, reporting on the ASHRAE research behind the ASHRAE/ADI duct calculator, notes that compression “increases the roughness and, therefore, the friction loss inside a flexible duct.” In Energy Vanguard’s example, 400 CFM that fits a 10 in flex duct pulled tight needs a 12 in duct if the liner is left with 4% compression.
The duct size alone does not choose the fan. Add up the pressure loss along the longest run: the straight duct (the Check tab gives friction × length), the fittings, grilles, filters and any heat exchanger. Then pick a fan whose curve delivers your airflow at that pressure, not just at free air.
To see where a fan will actually run on its curve in your system, use the static pressure guide and operating point calculator.
A ductulator is a duct sizing calculator. It started as a cardboard wheel or slide rule: you line up the airflow with the friction rate and read the duct size and velocity. HPAC described the ASHRAE/ADI duct calculator as one that “resembles a wheel-type ductulator similar to those used during the days of slide rules”. This page does the same calculation on screen, in imperial or metric units.
About 10 in round at 0.1 in. w.g. per 100 ft (exact 9.7 in, 733 fpm in a 10 in duct). For a return run, use 12 in to stay under 700 fpm.
About 14 in round at 0.1 in. w.g. per 100 ft (exact 13.6 in). The air then moves at 935 fpm, which is above the 900 fpm residential supply limit, so a home supply trunk would go to 16 in.
286 mm exact at 0.8 Pa/m in galvanized steel, so 315 mm in practice (3.56 m/s). A 400 × 200 mm rectangular duct has about the same friction.
Calculate it: available static pressure × 100 ÷ total effective length of the longest run. 0.1 in. w.g. per 100 ft (about 0.8 Pa/m) is a common starting guess, and ACCA warns it can undersize the ducts when the real value is lower.
No. It sizes straight duct. Add the equivalent length of fittings to the run, or add their pressure losses separately when you total the system pressure for the fan.
Yes, choose “Flexible duct, pulled tight”. The result assumes the liner is fully stretched; compressed or sagging flex has a higher friction loss.
Need a fan for this duct? Send us the airflow, the duct size and the total pressure of your longest run, and we will match a KCVENTS inline, mixed flow or cabinet fan to it on the fan curve.