KCVENTSの最新情報
換気&HVACソリューション

気流工学に関する最新の知見、省エネ型全熱交換器(ERV)/熱交換換気システム(HRV)の最新情報、環境配慮型HVACソリューションをお届けするニュースレターにご登録ください。

KCVENTSから直接、限定技術ガイド、カスタムOEM/ODM対応力、世界各地の展示会ニュースをいち早くお届けします。

VT501 静音運転、風量、省エネ概要

Ductulator: Duct Size Calculator for Round and Rectangular Ducts

Enter the airflow and either a design friction rate or a maximum air velocity. This ductulator returns the round duct diameter, the next common size, rectangular ducts with the same pressure loss, and the velocity and friction you will actually get at each size. It works in CFM and inches or in m³/h and millimetres.

CFM
in. w.g. / 100 ftPa/m
fpmm/s
inmm
×inmm
ftm

Air at 20 °C (68 °F) at sea level. Straight duct only: add fittings separately.

Exact round diameter
–
Next common size
–
Velocity at this size–
Friction at this size–
Velocity pressure–
The velocity is above 900 fpm (4.6 m/s), the Manual D maximum for residential supply ducts. Choose a larger size if this is a home supply run.
The velocity is above 700 fpm (3.6 m/s), the Manual D maximum for residential return ducts.
This airflow is beyond the common sizes listed here. Use the rectangular options or split the airflow.

Rectangular ducts with the same friction

Width × heightAspect ratioEquivalent roundVelocityFriction rate

Widths are rounded up to the next 2 in (50 mm), so each rectangle has a slightly lower friction rate than the target. Aspect ratios above 4:1 are left out.

KCVENTS inline duct fans for this connection size

    Above 315 mm (12 in), duct fans are chosen on the fan curve: see the cabinet fans または send us your airflow and pressure.

    Air velocity
    –
    Friction rate
    –
    Loss over this length–
    Equivalent round–
    Velocity pressure–
    The velocity is above 900 fpm (4.6 m/s), the Manual D maximum for residential supply ducts.
    The velocity is above 700 fpm (3.6 m/s), the Manual D maximum for residential return ducts.

    How to size a duct in three steps

    1. Find the airflow for each run. Start from the room or equipment airflow. If you only know the room, the ventilation CFM calculator turns room size and air changes per hour into CFM and m³/h.
    2. Set a friction rate, or a velocity limit. The friction rate is how much pressure you can afford to lose per 100 ft (or per metre) of duct. It comes from the fan’s available pressure and the length of the longest run (next section).
    3. Read the diameter, then check the velocity. Round up to a size you can buy. If the velocity at that size is too high for the space, go one size up. Ducts that are too fast are noisy, and ducts that are too small starve the rooms at the end of the run.

    Worked example: 400 CFM

    With a design friction rate of 0.073 in. w.g. per 100 ft, the calculator gives an exact diameter of 10.35 in. Energy Vanguard ran the same 400 CFM at 0.073 through the ASHRAE duct calculator wheel and needed “a round metal duct that’s slightly larger than 10″”. In a 10 in duct the air moves at 733 fpm with 0.086 in. w.g. per 100 ft, which is fine for a supply run. A return carrying 400 CFM needs a 12 in duct (509 fpm, 0.036 in. w.g. per 100 ft) to stay under the 700 fpm return limit.

    Worked example: 1,000 m³/h

    At 0.8 Pa/m in galvanized steel, 1,000 m³/h needs 286 mm. The next common size is 315 mm: 3.56 m/s and 0.50 Pa/m. A 400 × 200 mm rectangle has the same friction as a 305 mm round duct.

    Which friction rate to use

    The friction rate is not a constant you pick from a chart. ACCA’s Manual D calculates it from two numbers: the available static pressure (ASP) and the total effective length (TEL) of the longest run.

    “The available static pressure (ASP) is what’s left when you take the total external static pressure and subtract the pressure drops for all the things that aren’t ducts and fittings.” – ACCA, Calculating Friction Rate – It’s Not a Constant (2017)
    “The total effective length (TEL) is the sum of the duct lengths and the fitting equivalent lengths.” – ACCA (2017)

    Friction rate (in. w.g. per 100 ft) = ASP × 100 ÷ TEL

    Many installers skip the calculation and use 0.1 in. w.g. per 100 ft. ACCA explains that 0.1 sits in the middle of the Manual D chart, which is why it became a habit, and that in one worked design “if you use 0.1 instead of 0.073, your ducts will be undersized.” Use the calculated value when you have it, and 0.1 only for a first estimate.

    in. w.g. per 100 ftPa per metre
    0.050.41
    0.080.65
    0.100.82

    Velocity limits

    Sizing by friction alone can leave air moving too fast. Energy Vanguard summarises the residential limits in ACCA Manual D: “In Manual D, Table N3-1 specifies the maximum velocities for supply and return trunks and branches. For supplies, it’s 900 fpm. For returns, it’s 700 fpm.” That is 4.6 m/s and 3.6 m/s. The calculator warns you when the size you picked is above either limit. Commercial and industrial ducts are often designed faster, so use the limit your project specifies.

    Quick reference: duct size by airflow

    Galvanized round duct, sized at 0.1 in. w.g. per 100 ft and rounded up to the next common size (1 in steps up to 10 in, then 2 in steps).

    風量Exact diameterDuct sizeVelocity at that size
    100 CFM5.8 in6 in509 fpm
    200 CFM7.5 in8 in573 fpm
    400 CFM9.7 in10 in733 fpm
    600 CFM11.3 in12 in764 fpm
    800 CFM12.6 in14 in748 fpm
    1,000 CFM13.6 in14 in935 fpm
    1,500 CFM15.9 in16 in1,074 fpm
    2,000 CFM17.7 in18 in1,132 fpm

    The same in metric, sized at 0.8 Pa/m:

    風量Exact diameterDuct sizeVelocityFriction at that size
    100 m³/h122 mm125 mm2.26 m/s0.70 Pa/m
    200 m³/h157 mm160 mm2.76 m/s0.73 Pa/m
    300 m³/h183 mm200 mm2.65 m/s0.52 Pa/m
    500 m³/h221 mm250 mm2.83 m/s0.44 Pa/m
    1,000 m³/h286 mm315 mm3.56 m/s0.50 Pa/m
    1,500 m³/h332 mm355 mm4.21 m/s0.58 Pa/m
    2,000 m³/h370 mm400 mm4.42 m/s0.55 Pa/m
    3,000 m³/h431 mm450 mm5.24 m/s0.65 Pa/m

    Round or rectangular duct

    A rectangular duct carrying the same airflow with the same friction is not the one with the same area. Huebscher’s equation gives the round diameter with equal friction:

    De = 1.30 × (a × b)^0.625 ÷ (a + b)^0.25

    A 10 × 16 in duct, for example, behaves like a 13.7 in round duct. For a 300 mm round duct (0.071 m² of area, 0.94 m of perimeter), the equal-friction rectangles in 50 mm steps are 400 × 200 mm (0.080 m², 1.20 m) and 300 × 300 mm (0.090 m², 1.20 m). The rectangle always needs more sheet metal per metre. The flatter it gets, the more it needs, so keep the aspect ratio low when the ceiling allows.

    Duct material and flexible duct

    Rougher walls need bigger ducts. The calculator uses the roughness classes from Caleffi’s duct pressure loss handbook: 0.03 mm for PVC and aluminium, 0.09 mm for galvanized and stainless steel, 0.9 mm for lined ducts and 3.0 mm for flexible ducts. For 720 m³/h at 0.8 Pa/m, that means 250 mm in PVC, 253 mm in galvanized steel, 268 mm in lined duct and 282 mm in flexible duct.

    Flexible duct is only as good as its installation. HPAC, reporting on the ASHRAE research behind the ASHRAE/ADI duct calculator, notes that compression “increases the roughness and, therefore, the friction loss inside a flexible duct.” In Energy Vanguard’s example, 400 CFM that fits a 10 in flex duct pulled tight needs a 12 in duct if the liner is left with 4% compression.

    From duct size to fan

    The duct size alone does not choose the fan. Add up the pressure loss along the longest run: the straight duct (the Check tab gives friction × length), the fittings, grilles, filters and any heat exchanger. Then pick a fan whose curve delivers your airflow at that pressure, not just at free air.

    To see where a fan will actually run on its curve in your system, use the static pressure guide and operating point calculator.

    Assumptions and limits

    • Air at 20 °C and sea level (density 1.204 kg/m³). Hot air, cold air and high altitude change the result.
    • Straight duct only. Elbows, tees, dampers and grilles add losses that a full design (ACCA Manual D, ASHRAE duct design) accounts for.
    • Friction from the Darcy equation with the Altshul–Tsal friction factor; rectangular equivalents from Huebscher. Both formulas are given in the Caleffi handbook listed below.
    • “Common sizes” are 80–1,250 mm in metric and 3–48 in in imperial (1 in steps to 10 in, then 2 in). Check what your supplier stocks.

    よくある質問

    What is a ductulator?

    A ductulator is a duct sizing calculator. It started as a cardboard wheel or slide rule: you line up the airflow with the friction rate and read the duct size and velocity. HPAC described the ASHRAE/ADI duct calculator as one that “resembles a wheel-type ductulator similar to those used during the days of slide rules”. This page does the same calculation on screen, in imperial or metric units.

    What size duct do I need for 400 CFM?

    About 10 in round at 0.1 in. w.g. per 100 ft (exact 9.7 in, 733 fpm in a 10 in duct). For a return run, use 12 in to stay under 700 fpm.

    What size duct do I need for 1,000 CFM?

    About 14 in round at 0.1 in. w.g. per 100 ft (exact 13.6 in). The air then moves at 935 fpm, which is above the 900 fpm residential supply limit, so a home supply trunk would go to 16 in.

    What duct size for 1,000 m³/h?

    286 mm exact at 0.8 Pa/m in galvanized steel, so 315 mm in practice (3.56 m/s). A 400 × 200 mm rectangular duct has about the same friction.

    What friction rate should I use?

    Calculate it: available static pressure × 100 ÷ total effective length of the longest run. 0.1 in. w.g. per 100 ft (about 0.8 Pa/m) is a common starting guess, and ACCA warns it can undersize the ducts when the real value is lower.

    Does the calculator include elbows and fittings?

    No. It sizes straight duct. Add the equivalent length of fittings to the run, or add their pressure losses separately when you total the system pressure for the fan.

    Can I use it for flexible duct?

    Yes, choose “Flexible duct, pulled tight”. The result assumes the liner is fully stretched; compressed or sagging flex has a higher friction loss.

    Need a fan for this duct? Send us the airflow, the duct size and the total pressure of your longest run, and we will match a KCVENTS inline, mixed flow or cabinet fan to it on the fan curve.

    Ask for a fan selection

    出典